DISTRIBUTOR
A
· WIRING
Phase 3 · simulator · external events · trips · readings
Sliders + buttons drive faults · click
tripped handle
to reset
Reset all
PHASE
3
/ 3
L1
L2
L3
N
PE
CTRL
24 V / sense
dim
= de-energized
● bus tap · solid = busbar · dashed = control wire
NORMAL — power via A7 + A8 contactor
All 4 outputs LIVE
Loads:
A11.1
50%
A11.2
50%
A11.3
50%
A11.4
50%
L-N voltage
230 V
Faults:
⚡ Lightning
Ground fault
100 mA
300 mA
500 mA
Phase loss
L1
L2
L3
✕ N loss
✕ VMR fault
✕ SPD blow
Reset:
events
trips
Scenarios:
1. Норма
2. Перегруз A11.2
3. Утечка 100 mA
4. Утечка 500 mA
5. VMR fault
6. Молния
7. Молния+SPD✕
8. Обрыв N
9. Обрыв L1
10. Просадка 170 V
L1
L2
L3
N
PE
A0
CEE INLET 125 A
5P · 6h · red · 400 V · IP67
L1
L2
L3
N
PE
A1
SWITCH-DISCONNECTOR 4P
160 A · AC-23A · lockable · OPTIONAL
ON
A2
MAIN MCCB 4P · 125 A
Icu ≥ 25 kA · overcurrent / SC
ON
— A3 SPD BRANCH —
MCB
SPD BACKUP · 4P
per datasheet
ON
A3
SPD · TYPE 1+2
3P+N → PE
Iimp ≥ 12.5 kA · Up ≤ 1.5 kV
OK
PE
— AUX MCB → A4 + A6 —
AUX
MCB · 4P
B-curve · 6 A
shared: A4 + A6
ON
A4
MULTIMETER
V1 230 V2 230 V3 230
I1 016 I2 016 I3 016
Hz 50 kW 11.0
V-IN
CT
A6
RCM · MONITOR
mA 0
STATUS NORMAL
SUPPLY
CT
CT·L1
CT·L2
CT·L3
— A5 INDICATOR (own fuse, independent of aux MCB) —
FUSE
own fuse
independent of aux MCB
ON
A5
PHASE INDICATOR
3 × LED · L1/L2/L3 → N
L1
L2
L3
N
L1
L2
L3
— A6 · CT RING (encircles L1+L2+L3+N · PE excluded) —
CT around L1+L2+L3+N · PE passes outside the ring →
— A9 · MANUAL BYPASS · 4P SPDT —
A9
MANUAL BYPASS · 4P SPDT (12 contacts)
160 A · AC-23A · key-operated · lockable in both positions
NORMAL
A7
RCCB · TYPE A · S · 4P
125–160 A · IΔn = 300 mA · selective
ON
A8
PROTECTION ASSEMBLY · VMR + COIL SUPPLY + CONTACTOR
A8.4
CONTACTOR 4P
160 A · AC-1 · 24 V DC coil
L1/L2/L3/N · coil A1/A2
A1+
A2−
CLOSED
A8.1
U-RELAY · VMR
U-min/max · N-loss · NO contact 11–14
L1
L2
L3
N
A1+
A2−
14
11
NO 11–14
A8.2
B6 · 1P+N
coil supply
L
N
ON
A8.3
PSU 230AC →
24 V DC
L
N
+24
0V
— BYPASS CORRIDOR (from A9 BYPASS pins) → MERGE BUS —
A10.1
MCB · C32 · 4P
Icn ≥ 10 kA
ON
A10.2
MCB · C32 · 4P
Icn ≥ 10 kA
ON
A10.3
MCB · C32 · 4P
Icn ≥ 10 kA
ON
A10.4
MCB · C32 · 4P
Icn ≥ 10 kA
ON
A11.1 · CEE 32 A
A11.2 · CEE 32 A
A11.3 · CEE 32 A
A11.4 · CEE 32 A
— PE BAR · CONTINUOUS · NEVER SWITCHED · NEVER BYPASSED —
A0 inlet PE → enclosure → A3 SPD discharge → all 4 outlets PE
PE never passes through A6 RCM CT ring